Honevwell
THE Y343B IGNITION PACKAGE PROVIDES
DIRECT SPARK IGNITION (DSI) FOR GAS
HEATING SYSTEMS. THE PACKAGE IN-
CLUDES THE S87D ELECTRONIC MODULE,
Q354A FLAME SENSOR, Q347A SPARK IG-
NITER-SENSOR AND 392286-l IGNITION
CABLE.
DEPENDABLE BURNER IGNITION
0 Spark generated by electronic module and
internal step-up transformer.
SOLID STATE DESIGN
17 Compact, solid state components provide
accurate, long-lasting performance.
0 No mechanical friction or wear.
MAXIMUM OPERATING SAFETY
0 Proves presence of flame on burner igni-
tion, then protects against burner flame-out
and interruption of electric power or gas sup-
ply during run cycle.
0 Open or short circuit in any electronic com-
ponent results in safety shutdown.
USES FLAME RECTIFICIATION PRINCIPLE
0 Any false flame signal, including electrical
short or ground, results in safety shutdown.
0 Ignition is started, main burner is ignitied,
burner flame is proved and continuously
monitored during main burner-on period. lg-
nition spark is discontinued when flame is
proved.
CONVENIENT REMOTE
RESTART PROCEDURE
0 After safety shutdown, equipment must be
manually reset from remote thermostat or
temperature controller.
0 System automatically locks out after
trial-for-ignition. If malfunction exists, correc-
tion must be made before system is manually
reset.
LOW VOLTAGE CONTROL CIRCUIT
0 Permits use of 24 V thermostat for op-
timum temperature control.
0 Reduced wiring costs - both on appliance
and on job.
GAS VALVE CONTROL
0 S87D internal relay switches the gas valve
on and off.
0 System can be used with a P-stage gas
valve, if desired.
ALARM CONTROL
El Optional alarm circuit provides 24 Vat for
an automatic visual or audible signal if any
part of system malfunctions and causes a
lockout.
L.H.
Form Number 68-0014
1-630 0 Honeywell Inc. 1983
Vista de pagina 0
1 2 3 4 5 6 ... 10 11

Indice de contenidos

Pagina 1 - Honevwell

Honevwell THE Y343B IGNITION PACKAGE PROVIDES DIRECT SPARK IGNITION (DSI) FOR GAS HEATING SYSTEMS. THE PACKAGE IN- CLUDES THE S87D ELE

Pagina 2 - SPECIFICATIONS

GROUNDING CONNECTIONS A common ground is required for the burner, spark igniter-sensor mounting bracket and the GND terminal of the 5

Pagina 3 - 392286-l IGNITION CABLE

t TROUBLESHOOTING . Start the system by setting the thermostat (tem- down to the next box. If the condition is not true or not perat

Pagina 4 - ;NSlAL~~lON *

SPECIFICATIONS 4 The Y34381002 Direct Soark Gas Burner lanition Package includes the S87D ilectronic Module, 6347A Spark Igniter-Sensor,

Pagina 5 - 1 .o 0.2

AMBIENT TEMPERATURE RATING: Minus 40 F to plus 175 F [minus 40 C to plus 79 C]. WIRING CONNECTIONS: l/4 in. [6.4 mm] male quick-c

Pagina 6 - AUXILIARY CONTROLS

TABLE l-GAS CONTROLS. MODEL NO. V845A VR8450A V845C VR8450C VR8540A VR8590A VR8600A TYPE OF PRESSURE REGULATOR Standard Standard Step-open Step-o

Pagina 7 - _^.,” ~.. ,, ,IX ^ _

Position the Q347 so that only the tips of the elec- trodes are immersed in the burner flame. The burner must ignite smoothly -

Pagina 8 - OPERATION

Q354A FLAME SENSOR 1. Mate quick-connect terminals (l/4 in. [6.4 mmf)’ are provided on both the Q354 and S87D. Connect the SENSOR t

Pagina 9 - SERVICE

FIG. B-WIRING HOOKUP FOR Y343B PACKAGE IN A TYPICAL TWO-STAGE DSI HEATING SYSTEM. ,, “,, ~ ,,, I ,,,, ,. ,.., :. II ,, , .xI,. j ,

Pagina 10 - CHECKOUT AFTER SERVICE

STARTUP AND CHECKOUT The following start-up and checkout procedures are basic to the S87. If possible, refer to the specific instruct

Pagina 11 - TROUBLESHOOTING

FIG. a--NORMAL SYSTEM SEQUENCE OF OPERATION. SERVICE l Only persons trained and experienced in DSI systems should service this equipment