Honeywell 301c Manual de usuario Pagina 93

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 228
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 92
M-510324 301C User Manual 91
7/10 Honeywell
BACnet/IP MODULE
BACnet/IP MODULE
(BIP option)
Specifications
Ethernet Port : 10/100-compatible with 10 Base-T interface, RJ-45
Visual Indicators : Green LED LINK
Yellow LED ACT
Network Configuration: See 301C BACnet menu section.
BACnet/IP protocol
UDP Port: 47808. This value is not modifiable using the 301C.
The module has been developed as per ANSI/ASHRAE Standard 135-
2001 : BACnet®— A Data Communication Protocol for Building
Automation and Control Networks. The Data Link Layer option is per
BACnet/IP (Annex J).
http://www.ashrae.org/
BACnet Objects
BACnet objects represent any information available through the 301C
sub network. Each available value is represented by one object of a
specific type. There are currently 6 object types supported :
Analog Input represented by ‘AI’
Analog Value represented by ‘AV’
Binary Input represented by ‘BI’
Binary Output represented by ‘BO’
Binary Value represented by ‘BV’
Device represented by ‘DEV’
Vista de pagina 92
1 2 ... 88 89 90 91 92 93 94 95 96 97 98 ... 227 228

Comentarios a estos manuales

Sin comentarios