® U.S. Registered Trademark
Copyright © 2001 Honeywell• All Rights Reserved
INSTALLATION INSTRUCTIONS
69- 1465- 3
T8001F, T8024F Flush Mount
Programmable Thermostat
APPLICATION
The T8001F Thermostat provides single-stage,
programmable temperature control for 24 Vac heating-
cooling systems with manual changeover from heat to
cool. The T8024F Thermostat provides multistage
electronic control of single-zone heating and cooling
systems. Heating cycle rate is selectable at 1, 3, 4, 5, 6,
9, or 12 cph. Cooling cycle rate is fixed at 3 cph.
Temperature indication can be set for °F or °C.
The T8001F, T8024F Thermostat is powered directly
from the system transformer. Batteries are not required
because setpoints are held permanently by non-volatile
memory.
The T8001F, T8024F model includes a thermostat,
wallplate and owner’s guide. See Table 1.
MERCURY NOTICE
If this control is replacing a control that contains
mercury in a sealed tube, do not place your old
control in the trash. Dispose of it properly.
Contact your local waste management authority
for instructions regarding recycling and the
proper disposal of the control.
INSTALLATION
When Installing this Product…
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazard-
ous condition.
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable for
your application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
CAUTION
Hazardous Voltage.
Can damage heating/cooling system.
Disconnect power at furnace or main breaker/
fuse box.
Location
Install the thermostat about 5 ft (1.5m) above the floor in
an area with good air circulation at average temperature.
See Fig. 1. Do not install the thermostat where it can be
affected by:
drafts or dead spots behind doors and in corners.
hot or cold air from ducts.
radiant heat from the sun or appliances.
concealed pipes and chimneys.
unheated (uncooled) areas such as an outside wall
behind the thermostat.
Installing Wallplate in Wall
IMPORTANT
Level only for appearance. The thermostat func-
tions normally even when not level.
Mount wallplate and the T8001F or T8024F with the wing
anchors provided (see Fig. 2) as follows:
1. Place the wallplate template at the desired location
on the wall.
2. Trace and cutout the opening.
3. Pull the thermostat wire through the wallplate
entrance hole.
4. Fasten the wallplate to the wall using the wing
anchors.
Table 1. Thermostat Descriptions.
Model System Changeover System Selection Fan Selection Powering Method
T8001F Heat-Cool Manual Cool-Off-Heat Auto-On Hardwired
T8024F Heat-Cool Manual Cool-Off-Heat Auto-On Hardwired
Vista de pagina 0
1 2 3 4 5 6 7 8

Indice de contenidos

Pagina 1 - Programmable Thermostat

® U.S. Registered TrademarkCopyright © 2001 Honeywell • • All Rights Reserved INSTALLATION INSTRUCTIONS69- 1465- 3T8001F, T8024F Flush

Pagina 2 - 69-1465—3 2

T8001F, T8024F FLUSH MOUNT PROGRAMMABLE THERMOSTAT69-1465—3 2Fig. 1. Typical location of thermostat.Fig. 2. Mounting wallplate to wall.WiringIMPORTANT

Pagina 3 - 3 69-1465—3

T8001F, T8024F FLUSH MOUNT PROGRAMMABLE THERMOSTAT3 69-1465—3Fig. 4. T8024F wiring connections.Fig. 5. Restrict wiring to shaded area (T8001 shown).Th

Pagina 4 - INSTALLER SETUP

T8001F, T8024F FLUSH MOUNT PROGRAMMABLE THERMOSTAT69-1465—3 4Setting Fan Operation (Fuel) Switch (T8001F Only)The fan operation (fuel) switch is prese

Pagina 5 - 5 69-1465—3

T8001F, T8024F FLUSH MOUNT PROGRAMMABLE THERMOSTAT5 69-1465—33. Setting Number of Cool/Heat Stages (T8024F Only).a. Press ▲ to display number of cool

Pagina 6 - OPERATION

T8001F, T8024F FLUSH MOUNT PROGRAMMABLE THERMOSTAT69-1465—3 6OPERATIONSetting FAN and SYSTEM SwitchesFan and system settings are controlled manually b

Pagina 7 - CHECKOUT

T8001F, T8024F FLUSH MOUNT PROGRAMMABLE THERMOSTAT7 69-1465—3CHECKOUTHeating1. Slide the SYSTEM switch to Heat and the FAN switch to Auto.2. Press and

Pagina 8

69-1465—3 G.H. Rev. 9-01 Printed in Mexico www.honeywell.com/yourhomeT8001F, T8024F FLUSH MOUNT PROGRAMMABLE THERMOSTATHome and Building Control H

Comentarios a estos manuales