PRODUCT DATA
60- 2026- 11
® U.S. Registered Trademark
Copyright © 2001 Honeywell • All Rights Reserved
C7027A, C7035, C7044A, C7927A
Minipeeper® Ultraviolet Flame Detectors
APPLICATION
The C7027A, C7035A, C7044A and C7927A Minipeeper®
Ultraviolet Flame Detectors detect the ultraviolet radiation
emitted by combustion flames. The flame detectors are used
with Honeywell flame safeguard controls to provide flame
supervision for gas, oil, or combination gas-oil burners.
FEATURES
C7027A, C7035A, and C7044A Flame Detectors are
used with RA890G devices or R7249A, R7290A,
R7749B and R7849A,B Amplifiers and the appropriate
Honeywell controls.
C7044A may also be used with the following 50 Hz
Honeywell combustion controls/amplifiers:
R4341/R7323
R4343/R7323
R4344/R7323
C7027A has an integral collar threaded (internal
1/2-14 NPSM) for mounting on a one-half-inch sight
pipe.
C7035A has an integral collar threaded (internal
1-11-1/2 NPSM) for mounting on a one-inch sight pipe.
C7035A housing meets Underwriters Laboratories Inc.
requirements for rain tightness and complies with
NEMA enclosure standards, types 4 and 4X.
C7044A mounts with a two screw bracket. The UV
sensor tube is enclosed in a stainless steel housing.
C7044A has the capability of side or end viewing in
flame monitoring applications.
Because of their compact size, the C7027A and
C7044A are particularly suitable for blast tube
mounting.
Properly installed, the C7027A, C7035A and C7927 are
pressure rated for 5 psi.
C7035A ultraviolet radiation sensor tube is field
replaceable.
Two C7027A, C7035A or C7044A Flame Detectors can
be wired in parallel for difficult flame sighting
installations.
C7927A is used with only the R7851B Flame Amplifier
and the 7800 SERIES controls.
C7927A has an integral collar threaded (internal
1/2-14 NPSM) for mounting on a one-half inch sight
pipe.
C7027A
C7035A
C7044A
C7927A
Contents
Application ........................................................................ 1
Features ........................................................................... 1
Specifications ................................................................... 2
Ordering Information ........................................................ 2
Wiring (All Models—Fig. 10) ............................................. 8
Adjustments and Checkout .............................................. 9
Troubleshooting ................................................................ 12
Maintenance ..................................................................... 12
Vista de pagina 0
1 2 3 4 5 6 ... 11 12

Indice de contenidos

Pagina 1 - C7027A, C7035, C7044A, C7927A

PRODUCT DATA60- 2026- 11® U.S. Registered TrademarkCopyright © 2001 Honeywell • All Rights Reserved C7027A, C7035, C7044A, C7927AMinipeeper® Ultravio

Pagina 2 - SPECIFICATIONS

C7027A, C7035, C7044A, C7927A MINIPEEPER® ULTRAVIOLET FLAME DETECTORS60-2026—11 10Fig. 10. Measuring microamp flame signal.The R7749B and R7849A,B Amp

Pagina 3 - 3 60-2026—11

11 60-2026—11a Currently obsolete.Ignition Spark Response TestTest to be sure that ignition spark is not actuating the flame relay (usually 2K) or fla

Pagina 4 - INSTALLATION

60-2026—11 G.R. Rev. 07-01 www.honeywell.com/bbcHome and Building Control Home and Building ControlHoneywell Honeywell Limited-Honeywell Limitée1

Pagina 5 - By The UV Detector

C7027A, C7035, C7044A, C7927A MINIPEEPER® ULTRAVIOLET FLAME DETECTORS60-2026—11 2ORDERING INFORMATIONWhen purchasing replacement and modernization pro

Pagina 6 - Sight Pipe Ventilation

C7027A, C7035, C7044A, C7927A MINIPEEPER® ULTRAVIOLET FLAME DETECTORS3 60-2026—11C7035A Minipeeper® Ultraviolet Flame Detector:Flame Detection: End vi

Pagina 7 - Mount The Detector (Fig. 7)

C7027A, C7035, C7044A, C7927A MINIPEEPER® ULTRAVIOLET FLAME DETECTORS60-2026—11 4Fig. 4. Installation dimensions of C7927A1016 (U.S.A. version) and C7

Pagina 8 - WIRING (ALL MODELS—FIG. 10)

C7027A, C7035, C7044A, C7927A MINIPEEPER® ULTRAVIOLET FLAME DETECTORS5 60-2026—11WARNINGExplosion Hazard and Electrical Shock Hazard.Can cause serious

Pagina 9 - ADJUSTMENTS AND CHECKOUT

C7027A, C7035, C7044A, C7927A MINIPEEPER® ULTRAVIOLET FLAME DETECTORS60-2026—11 6Mounting a C7027A, C7927 or C7035ALocate the Sight PipeThe location

Pagina 10 - Pilot Turndown Test

C7027A, C7035, C7044A, C7927A MINIPEEPER® ULTRAVIOLET FLAME DETECTORS7 60-2026—11Swivel MountTo facilitate proper sighting of the flame, a swivel moun

Pagina 11 - Final Checkout

C7027A, C7035, C7044A, C7927A MINIPEEPER® ULTRAVIOLET FLAME DETECTORS60-2026—11 8Fig. 8. Mounting C7044A Detector on blast tube.The C7044 is mounted i

Pagina 12 - MAINTENANCE

C7027A, C7035, C7044A, C7927A MINIPEEPER® ULTRAVIOLET FLAME DETECTORS9 60-2026—11g. The scanner wires should remain separated a minimum of two in. (51