Honeywell Universal Digital Controller UDC 3300 Manual de usuario Pagina 205

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 294
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 204
4/00 UDC 3300 Controller Product Manual 193
5.20 Fuzzy Overshoot Suppression
Introduction
Fuzzy Overshoot Suppression minimizes overshoot after a setpoint change
or a process disturbance. This is especially useful in processes which
experience load changes or where even a small overshoot beyond the
setpoint may result in damage or lost product.
How it works
The fuzzy logic observes the speed and direction of the PV signal as it
approaches the setpoint and temporarily modifies the internal controller
response action as necessary to avoid an overshoot. There is no change to
the PID algorithm, and the fuzzy logic does not alter the PID tuning
parameters. This feature can be independently enabled or disabled, as
required by the application, to work with TUNE On-Demand tuning, the
SP tuning algorithm, or Adaptive Tune.
Configuration
To configure this item, refer to Section 3 Configuration:
Set Up Group ACCUTUNE
Function Prompt FUZZY
Select ENABLE or DISABL (
or )
Vista de pagina 204